Manufacturers of portable electronic flow meters for commissioning HVAC water systems
COMDRONIC Ltd
Electronic Commissioning Meters
For water based HVAC systems
+44 (0) 1473 462036
Web portal.

Water/Glycol mixtures

Specific gravity values for water/ glycol mixtures.

 

Temperature % Glycol additive
Deg C 0 10 20 30 40 50 60 70 80 90 100
80     0.991 1.003 1.017 1.026 1.036 1.046 1.054 1.062 1.068
70   0.990 1.000 1.010 1.023 1.034 1.042 1.053 1.062 1.069 1.075
60   0.995 1.007 1.017 1.030 1.041 1.050 1.060 1.070 1.076 1.083
50   1.000 1.013 1.013 1.035 1.048 1.057 1.067 1.077 1.084 1.090
40 0.990 1.004 1.018 1.029 1.042 1.054 1.064 1.074 1.085 1.091 1.098
30 0.996 1.007 1.022 1.034 1.047 1.059 1.070 1.080 1.092 1.099 1.105
20 0.999 1.010 1.026 1.038 1.052 1.065 1.076 1.088 1.099 1.106 1.114
10 1.000 1.013 1.028 1.042 1.056 1.070 1.082 1.094 1.105 1.113 1.120
0 1.000 1.015 1.029 1.045 1.061 1.075 1.088 1.100 1.112 1.120 1.128
-10       1.048 1.065 1.079 1.092 1.107 1.118 1.127 1.135
-20         1.068 1.083 1.097 1.113 1.124 1.133 1.136
-30           1.087 1.100 1.118 1.128 1.137 1.137
-40             1.102 1.122 1.133 1.138 1.138